bms:bestpractice:water:legionella [2022/02/09 18:55] mkbms:bestpractice:water:legionella [2022/02/09 19:12] (current) – [Cold water] mk
Line 27: Line 27:
 === Recomendations / Best Practice === === Recomendations / Best Practice ===
  
-Recommendad operation temperature +Recommended operations temperature 
  
   * Minimum 50 °C   * Minimum 50 °C
   * Preferred 55 °C   * Preferred 55 °C
   * At most 60 °C   * At most 60 °C
-== Water heater == 
  
-With water heater you should raise temperature to above 65 °C for 10 minutes weekly, and keep the temperature at +And at least minimum of 50 °C in the entire pipe system.
  
 +=== Water heater ===
 +
 +With a water heater you should raise the temperature to above 65 °C for 10 minutes weekly, and keep the temperature at 
 +
 +=== Water heater with circulation ==
 +
 +With a water heater with circulation you should raise the temperature to above 65 °C measured in return temperature.
 +
 +=== Cold water ===
 +
 +At most 20 °C but recommended below 10 °C
 +
 +~~DISCUSSION~~
bms/bestpractice/water/legionella.1644429319.txt.gz · Last modified: 2022/02/09 18:55 by mk